Commercial Plan
Submittal Guidelines Checklist - Revised 04/11
Adopted Codes (with Village amendments):
- International Building Code (2009)
- International Residential Code (2009)
- International Fuel Gas Code (2009)
- International Mechanical Code (2009)
- International Energy Conservation Code (2009)
- International Property Maintenance Code (2009)
- International Existing Building Code (2009)
- National Electric Code (2008)
- Illinois State Accessibility Code (1997)
- Illinois State Plumbing Code (2004)
* REVISIONS – the Village of Minooka requires a submission
letter from the design professional identifying each change and
each revision must be bubbled or clouded with a key or notation
made to match revision block on drawings.
Plan Submittal: Four (4) Complete Sets of the
Following:
Architectural:
- Soils report
- Specification book (when applicable)
- Cover sheet to include the following:
- Building code summary (occupancy, construction type,
allowable area increase
- Project data (project name, architect, engineer,
contractor)
- Area summary (square foot of each occupancy)
- Drawing index
- Location map
- Exiting diagram (required exit locations, rated
corridors)
- Fire resistive wall, floor and ceiling assembly
schedule
- Site plan
- Civil engineering plans
- Landscape plans
- Floor plan, not less ¼” = 1’0”, large buildings over
50,000 square feet 1/8” =1’0”
- Exterior elevations
- Door/window schedules
- Interior elevations, floor and wall types
- Handicapped accessibility and restroom details
- ADAAG requirements
- Roof details
- Stair details
Structural:
- Foundation plan
- Roof framing plan
- Floor framing plan
- Foundation details
- Structural details (connections, posts, columns, beams,
headers, and joists)
- Shear wall plan
- Structural schedules, specifications and calculations
- Stamped truss drawings / calculations
- Provide complete general structural notes with all
disciplines to be performed by special inspection per
chapter 17 of the 2003 IBC. The agency to perform the
inspections is required to provide all necessary information
per 1703.1 at the time of submittal. The structural Engineer
is required to submit in writing final acceptance of all
special inspection reports before issuance of Certificate of
Occupancy
Mechanical:
- HVAC plan
- HVAC details
- HVAC schedules and specifications
- Fire barrier penetration protection details and
specifications
- Roof access details (ladder)
- For restaurants provide type 1 / type 2 hood schedules
and details
Plumbing:
- Waste and vent isometric
- Gas line isometric
- Waste fixture unit load schedule
- Water fixture unit load schedule
- Water service pressure loss calculations for domestic
and landscape
- Fire barrier penetration protection details and
specifications
- Backflow prevention details and specifications
- Domestic and landscape water meter locations.
- Interceptor and sample vault specifications and details
where applicable
Electrical:
- Electrical site plan
- Building electrical plan
- Power
- Lighting
- Electrical legend
- One-line diagram and service section detail with notes
including;
- Available inrush current (AIC)
- Feeder and conduit sizes
- Sizes and types of transformers
- All grounding and bonding including sizes of
grounding conductors and bonding jumpers
- Feeder schedule
- Panel schedules
- Emergency lights, exit signs (review chapter 10, 2003
IBC for exterior exit discharge lighting requirements)
- Series rated equipment: provide note and fault current
calculations
- Fire barrier penetration protection details and
specifications
- Equipment schedules
Fire Protection:
- Please contact Minooka Fire district for current
requirements at (815) 467-5637
 |